TWS (air/water exchangers)

Side-mounted air/water exchangers

Key features:

  • Easy installation (side mounting)
  • Extra flat dimensions
  • Virtually no maintenance required
  • Ideal for polluted environments or extreme temperatures
Request a quote Plans de découpe échangeurs air/eau TWS

In standard

  • Adjustable mechanical thermostat (preset to +35°C)
  • Copper tube heat exchanger with aluminum fins
  • Centrifugal fan
  • Solenoid valve for temperature control (on/off)
  • 3-meter power cable
  • IP55 waterproof seal
  • Electro-galvanized casing
  • RAL 7035 paint
  • Complete documentation
  • 18-month warranty (unless otherwise agreed)

Options and adaptations

  • Different voltages and frequencies than standard
  • UL listed
  • RAL paint color different from standard
  • Stainless steel casing

▶ TO BE SPECIFIED IN YOUR REQUEST

Technical specifications


TWS 10 CAI TWS 18 CAI TWS 25 CAI TWS 35 CAI TWS 45 CAI TWS 60 CAI
Power supply Type Single-phase Single-phase Single-phase Single-phase Single-phase Single-phase
V-Hz 230-1-50/60 230-1-50/60 230-1-50/60 230-1-50/60 230-1-50/60 230-1-50/60
Cooling power W10A35
(+10°C water inlet, +35°C ambient)
W 1000 1750 2500 3500 4500 6000
Power consumption W10A35
(+10°C water inlet, +35°C ambient)
W 29 75 80 130 160 160
Input current
nominal
A 0.17 0.36 0.33 0.55 0.71 0.71
Line protection A 2 2 2 2 2 2
Electrical connection mm² nc nc nc nc nc nc
Waterproof index IP 55 55 55 55 55 55
Nominal air flow m3/h 330 570 860 1050 1450 1450
Nominal water flow l/h 150 150 500 500 500 800
Maximum water pressure  bar 10 10 10 10 10 10
Hydraulic connection Type  1/2″ G 1/2″ G 1/2″ G 1/2″ G 1/2″ G 1/2″ G
Operating temperature
ambient mini / maxi
°C +1 / +70 +1 / +70 +1 / +70 +1 / +70 +1 / +70 +1 / +70
Regulation temperature
range mini / maxi
°C +20 / +46 +20 / +46 +20 / +46 +20 / +46 +20 / +46 +20 / +46
Noise level dB(A) 55 58 58 64 69 69
Dimensions

H (mm) 453 901 901 1148 1148 1502
L (mm) 311 398 398 398 398 450
P (mm) 115 137 137 163 163 163
Weights kg 12 18 19 29 30 40
Non-contractual values / More information about air conditioning and cooling systems can be found on AFCE.

 


Diagrams

(caption)

  • H: Height (see specifications table)
  • L: Width (see specifications table)
  • P: Depth (see specifications table)
  • D = 120 mm
  • E = 43 mm (TWS 18 & 25) / 42 mm (TWS 35 &45) / 39 mm (TWS 60)
  • F = 30 mm (TWS 18 &25) / 25 mm (TWS 35, 45 et 60)

 

Going further: TWS air/water exchangers performance curves


The attached diagrams allow you to compare the performance of our TWS air/water exchangers, to help you select the model that best suits your installation.

  • P = Cooling capacity of the unit (in W)
  • Tw = Water inlet temperature (in °C)
  • Ti = Internal temperature of the cabinet (in °C)

> Do you still have a doubt or a further question about these air/water exchangers? Contact us!

Discover similar air conditioning products


Air/water exchangers for computer racks and bays
Rack/bay air/water exchangers (air conditioning)
ECPO (air/water exchangers)
Read more
Side-mounted KWS air-water exchangers
Side-mounted air/water exchangers (air conditioning)
KWS (air/water exchangers)
Read more
Eurodifroid custom-made top-mounted air/water heat exchangers for air conditioning
Top-mounted air/water exchangers (air conditioning)
RFO (air/water exchangers)
Read more
TWS air/water exchangers for air conditioning
Side-mounted air/water exchangers (air conditioning)
TWS (air/water exchangers)
Read more
TWS air/water exchangers for air conditioning
Top-mounted air/water exchangers (air conditioning)
TFO (air/water exchangers)
Read more
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.