RFI (coolers)

CUSTOM-MADE water or oil coolers (chillers)

Key features:

  • 100% custom-made adaptation!
  • Cooling power from 3 to 260 kW
  • Compatible with water, glycol water, oil, emulsions...
  • Wide range of options and finishes
  • Available in HFO refrigerant gas version (low GWP)
  • DP (tankless) or D (tankless, pumpless) variants
Request a quote

In standard

  • Complete documentation
  • 18-month warranty (unless otherwise agreed)

On demand

  • EXTT version (outdoor installation)
  • HFO low GWP refrigerant gas version
  • DP (tankless) or D (tankless, pumpless) variant
  • Complete adaptation of the hydraulic circuit (pumps, tanks, valves, levels, connections, controllers, etc.)
  • Complete adaptation of the electrical circuit and control system (PID, differential control, remote control, communication protocol, alarms, redundancies, etc.)
  • Complete adaptation of the finish (water filters, air filters, stainless steel finish, special paint, etc.)

▶ TO BE SPECIFIED IN YOUR REQUEST

Assembling RFI 70 EXTT water cooler at Eurodifroid

Assembling RFI 70 EXTT water cooler

Final testings on RFI 750 cooler, with factory acceptance tests

Final testings on RFI 750 cooler

Stainless steel and 3 way valve can be fitted on demand, on any RFI coolers

Stainless steel and 3 way valve on a RFI 70

Water chillers electrical box

RFI 1200 electrical box

RFI 80 oil coolers with water condenser and hot gas injection

RFI 80 coolers with water condenser and hot gas injection

RFI 160 oil cooler with Harting fittings

RFI 160 oil cooler with Harting fittings

Technical specifications


Examples of achievements RFI 30 RFI 30 T RFI 120 T RFI 350 THI RFI 700 THI RFI 1200 THI RFI 2800 THQ
Oil version available?   YES YES
EXTT* version available?   YES YES YES YES YES YES YES
HFO** refrigerant available?   YES YES YES
Power supply Type Single-phase Three-phase Single-phase Three-phase Three-phase Three-phase Three-phase
V-Hz 230-1-50 400-3-50 230-1-50 400-3-50 400-3-50 400-3-50 400-3-50
Cooling power
(+10°C water outlet, +32°C ambient)
kW
3.2 3.2 12 34.8 69 120 254
Power consumption kW 2 2.25 10.5 17.7 33.6 62.8 118
Refrigerant Type R407C R407C R407C R410A R410A R410A R410A
Other available refrigerant Type R1234ze R513A
R123ze
R513A
R1234ze
R513A
Input current
nominal / maxi
A 10 / 55 5 / 30 10.5 / 72 30.8 / 136 59.2 / 164 104.6 / 188.5 200.6 / 330.8
Line protection A nc nc nc nc nc nc nc
Electrical connection mm² nc nc nc nc nc nc nc
Waterproof index IP nc nc nc nc nc nc nc
Nominal air flow m3/h 2000 2000 6000 14400 20500 37500 77800
Available water flow
mini / maxi
l/mn 3 / 41 3 / 41 30 /80 20 / 100 50 / 250 200 / 750 400 / 1200
Available water pressure
mini / maxi
 bar 1 / 2.6 1 / 2.6 1 / 2.6 1.6 / 2.7 1.5 / 3.3 1.4 / 2.45 1 / 2.15
Hydraulic connection Type  nc nc nc nc nc nc nc
Tank capacity l 30 30 100 150 240 240 400
Operating temperature
ambient mini / maxi
°C +10 / +40*** +10 / +40*** +10 / +40*** -15 / +43 -15 / +43 -15 / +41 -15 / +43
Regulation temperature
range mini / maxi
°C +5 / +20**** +5 / +20**** +5 / +20**** +10 / +25 +10 / +25 +10 / +25 +10 / +25
Noise level dB(A) 69 69 69 < 70 < 70 nc nc
Dimensions

H (mm) 1204 1204 1450 1868 2111 2140 2005
L (mm) 671 671 1100 1202 1450 2200 2104
P (mm) 759 759 840 1160 1308 1505 3598
Weights kg 135 135 300 nc nc nc nc
* EXTT version: device configured for outdoor installation
** HFO gas: low GWP refrigerant
*** Possibility to extend to -20 / +55
**** Possibility to extend to -30 / +40
Non-contractual values / More information about air conditioning and cooling systems can be found on AFCE.

 


Eco-friendly design on all our water / oil coolers

RFI: Your custom-made... and optimized coolers!

Our RFI water cooler (chiller) range is an ultra-modular solution with a wide variety of customization options.

Power, refrigerant, compressor type, hydraulic circuit, ventilation, controls… our engineering teams have complete control over all the unit’s parameters to configure it precisely to your needs.

And in addition to offering you a reliable, efficient product perfectly suited to your project, we also provide solutions to reduce your operating costs, such as:

  • Intelligent management of ventilation, compressor, and expansion valve variations;
  • Microchannel condensers (optimizing heat exchange surface area);
  • And floating high pressure (reducing ventilation based on ambient temperature).

The RFI range of water or oil coolers is our “standard” range for a 100% tailored and 100% optimized cooling solution!

Going further: our HFO refrigerant water / oil coolers (chillers)


The implementation of the future European F-gas standards will have/already has a major impact on all refrigeration equipment (new project, replacement of equipment, updating of fleets…).

At EURODIFROID, we already have water coolers (chillers), oil coolers (chillers) and industrial air conditioners compatible with these standards, and our teams are ready to support you in this transition.

And with us: turn a regulatory obligation into an opportunity to reduce your operating costs.

How?

Simply because the components needed to operate an HFO refrigeration circuit often natively incorporate more “intelligent” features, allowing for significant savings on the consumption costs of your water or oil chiller.

> Check out our COMPLETE HFO REPORT now and contact our experts to benefit from all their advice.

Discover other active coolers


ERI Integrated water coolers for industries
Active coolers (cooling)
ERI (coolers)
Read more
LABO water coolers, or chillers, range, at Eurodifroid
Active coolers (cooling)
LABO (coolers)
Read more
RFC range of water or oil coolers (chillers), by Eurodifroid
Active coolers (cooling)
RFC (coolers)
Read more
RFI oil / water coolers (chillers) range, made by Eurodifroid
Active coolers (cooling)
RFI (coolers)
Read more
TRA water or oil coolers, made by Eurodifroid
Active coolers (cooling)
TRA (coolers)
Read more
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.