RFC (coolers)

Active water coolers (chillers) for “small to medium power”

Key features:

  • Small and medium power coolers (200 to 3000 W)
  • Modular range with rapid availability
  • Compatible with water, glycol water, oil, emulsions...
  • Wide range of options and finishes
  • Available in HFO refrigerant gas version (low GWP)
  • DP (tankless) or D (tankless, pumpless) variants
Request a quote

In standard

  • Hermetic piston compressor
  • Electronic thermostat with digital display
  • Air or water condenser
  • Capillary tube expansion valve
  • Polyethylene tank (steel for oil versions)
  • Submerged evaporator
  • Circulation pump
  • Main switchWater level indicator
  • Drain valve
  • Textured RAL 7032 paint (7035 on RFC 08-14-19)
  • Lifting ring (on RFC 08-14-19)
  • High/low temperature alarm (on RFC 08-14-19)
  • General fault alarm with dry contact (on RFC 08-14-19)
  • Complete documentation
  • 18-month warranty (unless otherwise agreed)

Options and adaptations

  • EXTT version (outdoor installation)
  • HFO low GWP refrigerant gas version (on RFC 12 and RFC 20)
  • DP (tankless) or D (tankless, pumpless) variant
  • Special pump (centrifugal, etc.)
  • Flow controller (with or without indicator)
  • Electric water level indicator
  • Differential control
  • PID control
  • Water filter
  • Air filter
  • Water condenser
  • Stainless steel casing
  • Industrial connectors (Harting type)
  • RAL paint color other than standard

▶ TO BE SPECIFIED IN YOUR REQUEST

RFC 20 oil coolers manufacturing at Eurodifroid premisses in France

RFC 20 oil coolers manufacturing

Assembling a stainless steel RFC 20 water cooler

Stainless steel RFC 20 water cooler

RFC 20 water coolers (chiller) series on assembly line

Series of RFC 20 chillers

Special paint option on a RFC 30 water cooler (chiller)

Special paint on RFC 30 water cooler

Technical specifications


RFC 02 RFC 07 RFC 12 RFC 12 T RFC 20 RFC 20 T RFC 30
Oil version available?   YES YES
EXTT* version available?   YES YES YES YES YES YES YES
HFO** refrigerant available?   YES YES
Power supply Type Single-phase Single-phase Single-phase Three-phase Single-phase Three-phase Single-phase
V-Hz 230-1-50 230-1-50 230-1-50 400-3-50 230-1-50 400-3-50 230-1-50
Cooling power
(+10°C water outlet, +32°C ambient)
W
200 700 1200 1200 2200 2200 3000
Power consumption W 290 560 1150 1250 1400 1500 1500
Refrigerant Type R134a R134a R134a
or R1234yf
R134a R134a
or R1234yf
R134a R134a
Input current
nominal / maxi
A 2.3 / 8.8 3.7 / 15 7.3 / 26 3.2 / 10 7 / 31 3.7 / 13 6.2 / 22
Line protection A nc nc nc nc nc nc nc
Electrical connection mm² nc nc nc nc nc nc nc
Waterproof index IP nc nc nc nc nc nc nc
Nominal air flow m3/h 255 390 900 900 1100 1100 1100
Available water flow
mini / maxi
l/mn 1 / 9 1 / 9 3 / 41 3 / 41 3 / 41 3 / 41 3 / 41
Available water pressure
mini / maxi
 bar 0.5 / 3.5 0.5 / 3.5 1 / 2.6 1 / 2.6 1 / 2.6 1 / 2.6 1 / 2.6
Hydraulic connection Type  nc nc nc nc nc nc nc
Tank capacity l 5 8 8 8 30 30 30
Operating temperature
ambient mini / maxi
°C +10 / +40*** +10 / +40*** +10 / +40*** +10 / +40*** +10 / +40*** +10 / +40*** +10 / +40***
Regulation temperature
range mini / maxi
°C +5 / +20**** +5 / +20**** +5 / +20**** +5 / +20**** +5 / +20**** +5 / +20**** +5 / +20****
Noise level dB(A) < 69 < 69 < 69 < 69 < 69 < 69 < 69
Dimensions

H (mm) 260 310 360 360 450 450 950
L (mm) 410 460 550 550 660 660 515
P (mm) 410 620 660 660 760 760 590
Weights kg 20 36 48 70 71 95 120
* EXTT version: device configured for outdoor installation
** HFO gas: low GWP refrigerant
*** Possibility to extend to -20 / +55
**** Possibility to extend to -30 / +40
Non-contractual values / More information about air conditioning and cooling systems can be found on AFCE.
RFC 08 AHI RFC 14 AHI RFC 19 AHI
Oil version available?  
EXTT* version available?  
HFO** refrigerant version available?  
Power supply Type Single-phase Single-phase Single-phase
V-Hz 230-1-50/60 230-1-50/60 230-1-50/60
Cooling power
(+10°C water outlet, +32°C ambient)
W
900 [1100***] 1600 [1900***] 2200 [2550***]
Power consumption W 1400 [1600***] 1600 [2050***] 1900 [2100***]
Refrigerant Type R134a R134a R134a
Input current
maxi
A 6.3 [7.7***] 7.6 [8.9***] 7.8 [11.1***]
Line protection A nc nc nc
Electrical connection mm² nc nc nc
Waterproof index IP 44 44 44
Nominal air flow m3/h 1000 1000 1000
Available water flow
mini / maxi
l/mn 3 / 18 5 / 18 6.5 / 18
Available water pressure
mini / maxi
 bar 1 / 7.6 1 / 6.6 1 / 6
Hydraulic connection Type  F 1/2″ F 1/2″ F 1/2″
Tank capacity l 10 10 10
Operating temperature
ambient mini / maxi
°C +15 / +45 +15 / +45 +15 / +45
Regulation temperature
range mini / maxi
°C +8 / +25 +8 / +25 +8 / +25
Noise level at 1m dB(A) 56 56 56
Dimensions

H (mm) 367 367 367
L (mm) 454 454 454
P (mm) 725 725 725
Weights kg 52 54 55
* EXTT version: device configured for outdoor installation
** HFO gas: low GWP refrigerant
*** Values at 60 Hz
Non-contractual values / More information about air conditioning and cooling systems can be found on AFCE.

 


Diagrams

RFC 02-07-12-20 water coolers diagrams

RFC 30 water coolers diagrams

RFC 08-14-19 water coolers diagrams

More information about RFC coolers

RFC coolers are part of EURODIFROID’s standard solutions, capable of quickly meeting “classic” cooling needs (water, oil, mixtures, etc.).

We only need a few steps to define the right product, with the appropriate options, and deliver it to you in just a few days:

  1. Defining the power required for your installation (our RFC range covers needs from 200 to 3000 W);
  2. Specifying the hydraulic configuration (type of fluid to be cooled, selection with/without pump, with/without tank, etc.);
  3. Setting the control parameters (flow/pressure safety features, remote operation, etc.);
  4. and finally, choosing the finishes (color, casing, protection, filtration, etc.).

A range of coolers designed to be highly modular, in order to respond quickly and efficiently to “classic” small and medium power needs: laser, welding, linear motors, aquarium, electro-erosion, electro-spindles…

Going further: our HFO refrigerant water / oil coolers (chillers)


The implementation of the future European F-gas standards will have/already has a major impact on all refrigeration equipment (new project, replacement of equipment, updating of fleets…).

At EURODIFROID, we already have water coolers (chillers), oil coolers (chillers) and industrial air conditioners compatible with these standards, and our teams are ready to support you in this transition.

And with us: turn a regulatory obligation into an opportunity to reduce your operating costs.

How?
Simply because the components needed to operate an HFO refrigeration circuit often natively incorporate more “intelligent” features, allowing for significant savings on the consumption costs of your water or oil chiller.

> Check out our COMPLETE HFO REPORT now and contact our experts to benefit from all their advice.

Discover other active coolers


ERI Integrated water coolers for industries
Active coolers (cooling)
ERI (coolers)
Read more
LABO water coolers, or chillers, range, at Eurodifroid
Active coolers (cooling)
LABO (coolers)
Read more
RFC range of water or oil coolers (chillers), by Eurodifroid
Active coolers (cooling)
RFC (coolers)
Read more
RFI oil / water coolers (chillers) range, made by Eurodifroid
Active coolers (cooling)
RFI (coolers)
Read more
TRA water or oil coolers, made by Eurodifroid
Active coolers (cooling)
TRA (coolers)
Read more
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.