Accueil » Air conditioning » Ventilation » side-mounted fans » KVA (fans)
KVA (fans)
Side-mounted fans range
Key features:
- Quick assembly (using clips)
- Extra flat dimensions
- Included: fan + filter grid
- Wide range of electrical voltages
In standard
- Included: fan (blower) + grid with replaceable filter (KFA)
- Quick side mounting with clips
- Ball bearing fans (MTBF 30,000 h at 55 °C)
- Self-extinguishing according to UL 94-VO
- RAL 7035 or 7032 paint
- Complete documentation
- 18-month warranty (unless otherwise agreed)
Options and adaptations
- Numerous voltage options (24 VDC, 48 VDC, 115 VAC, 230 VAC, 400 VAC…)
- EMC (electromagnetic compatibility) versions
- Additional interchangeable filters (KFA type 25 / 50 / 100 / 200 / 500)
▶ TO BE SPECIFIED IN YOUR REQUEST
Technical specifications
| KVA 025-230 |
KVA 050-230 |
KVA 050-110 |
KVA 100-110 |
KVA 100-230 |
KVA 120-230 |
KVA 120-110 |
||
| Power supply | Type | AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Single-phase |
| V-Hz | 230-1-50/60 | 230-1-50/60 | 115-1-50/60 | 115-1-50/60 | 230-1-50/60 | 230-1-50/60 | 115-1-50/60 | |
| Power consumption | W | 13 (12*) | 22 (21*) | 22 (21*) | 22 (21*) | 22 (21*) | 24 (23*) | 24 (23*) |
| Input current nominal |
A | 0.10 (0.08*) | 0.14 (0.12*) | 0.26 (0.24*) | 0.26 (0.24*) | 0.14 (0.12*) | 0.15 (0.13*) | 0.30 (0.26*) |
| Electrical connection | mm² | FASTON 2.8 x 0.5 | FASTON 2.8 x 0.5 | FASTON 2.8 x 0.5 | FASTON 2.8 x 0.5 | FASTON 2.8 x 0.5 | FASTON 2.8 x 0.5 | FASTON 2.8 x 0.5 |
| Waterproof index | IP | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 |
| Nominal air flow | m3/h | 24 (28*) | 55 (60*) | 55 (60*) | 100 (110*) | 100 (110*) | 120 (130*) | 120 (130*) |
| Air flow with filter | m3/h | 14 (17*) | 40 (45*) | 40 (45*) | 75 (90*) | 75 (90*) | 92 (105*) | 92 (105*) |
| Type of filter | KFA 25 | KFA 50 | KFA 50 | KFA 100 | KFA 100 | KFA 200 | KFA 200 | |
| Air flow direction** | NORMAL | NORMAL | NORMAL | NORMAL | NORMAL | NORMAL | NORMAL | |
| Operating temperature ambient mini / maxi |
°C | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 |
| Noise level | dB(A) | 30 (35*) | 43 (49*) | 43 (49*) | 43 (49*) | 43 (49*) | 43 (49*) | 43 (49*) |
| Weights | kg | 0.38 | 0.78 | 0.78 | 1.00 | 1.00 | 1.25 | 1.25 |
| * Values at 60 Hz ** Airflow direction: N (normal) = from outside to inside / INV (reversed) = from inside to outside Non-contractual values |
||||||||
| KVA 200-230 |
KVA 200-110 |
KVA 500-230 |
KVA 500-110 |
KVA 500-110 inv |
KVA 500-400 |
||
| Power supply | Type | AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Single-phase |
AC – Alternating Three-phase |
| V-Hz | 230-1-50/60 | 230-1-50/60 | 230-1-50/60 | 115-1-50/60 | 115-1-50/60 | 230-1-50/60 | |
| Power consumption | W | 40 (38*) | 40 (38*) | 70 (90*) | 70 (90*) | 70 (90*) | 60 (70*) |
| Rated current nominal |
A | 0.17 (0.16*) | 0.34 (0.32*) | 0.40 (0.38*) | 0.80 (0.76*) | 0.80 (0.76*) | 0.18 (0.15*) |
| Electrical connection | mm² | FASTON 3 x 2.5 | FASTON 3 x 2.5 | FASTON 3 x 2.5 | FASTON 3 x 2.5 | FASTON 3 x 2.5 | FASTON 3 x 2.5 |
| Waterproof index | IP | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 |
| Nominal air flow | m3/h | 230 (260*) | 230 (260*) | 500 (570*) | 500 (570*) | 500 (570*) | 500 (570*) |
| Air flow with filter | m3/h | 95 (105*) | 180 (210*) | 370 (410*) | 370 (410*) | 370 (410*) | 370 (410*) |
| Type of filter | KFA 200 | KFA 200 | KFA 500 | KFA 500 | KFA 500 | KFA 500 | |
| Air flow direction** | NORMAL | NORMAL | NORMAL | NORMAL | REVERSE | NORMAL | |
| Operating temperature ambient mini / maxi |
°C | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 |
| Noise level | dB(A) | 53 (58*) | 53 (58*) | 65 (68*) | 65 (68*) | 65 (68*) | 65 (68*) |
| Weights | kg | 1.60 | 1.60 | 3.00 | 3.00 | 3.00 | 3.00 |
| * Values at 60 Hz ** Airflow direction: N (normal) = from outside to inside / INV (reversed) = from inside to outside Non-contractual values / More information about air conditioning and cooling systems can be found on AFCE. |
|||||||
| KVA 050-024 |
KVA 050-048 |
KVA 100-024 |
KVA 100-048 |
KVA 120-024 |
KVA 120-048 |
KVA 200-024 |
KVA 200-048 |
||
| Power supply | Type | DC – Direct | DC – Direct | DC – Direct | DC – Direct | DC – Direct | DC – Direct | DC – Direct | DC – Direct |
| V-Hz | 24 VDC | 48 VDC | 24 VDC | 48 VDC | 24 VDC | 48 VDC | 24 VDC | 48 VDC | |
| Power consumption | W | 9 | 13 | 9 | 13 | 9 | 13 | 26 | 33 |
| Rated current nominal |
A | 0.37 | 0.27 | 0.37 | 0.27 | 0.37 | 0.27 | 1.08 | 0.68 |
| Electrical connection | mm² | 2×1.5 | 2×1.5 | 2×1.5 | 2×1.5 | 2×1.5 | 2×1.5 | 2×1.5 | 2×1.5 |
| Waterproof index | IP | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 | 54 class 1 |
| Nominal air flow | m3/h | 55 | 55 | 100 | 100 | 120 | 120 | 180 | 180 |
| Air flow with filter | m3/h | 40 | 40 | 75 | 75 | 95 | 95 | 180 | 180 |
| Type of filter | KFA 50 | KFA 50 | KFA 100 | KFA 100 | KFA 200 | KFA 200 | KFA 200 | KFA 200 | |
| Air flow direction** | NORMAL | NORMAL | NORMAL | NORMAL | NORMAL | NORMAL | NORMAL | NORMAL | |
| Operating temperature ambient mini / maxi |
°C | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 | -10 / +70 |
| Noise level | dB(A) | 45 | 45 | 45 | 45 | 45 | 45 | 61 | 61 |
| Weights | kg | 0.47 | 0.47 | 0.70 | 0.70 | 0.95 | 0.95 | 1.2 | 1.2 |
| ** Airflow direction: N (normal) = from outside to inside / INV (reversed) = from inside to outside Non-contractual values / More information about air conditioning and cooling systems can be found on AFCE. |
|||||||||
Going further: selection of KVA fans
To help you select your product, EURODIFROID provides this fans selection diagram.
An example?
- You need a power dissipation (cooling) capacity of 500 W
- Your indoor/outdoor temperature difference is 20°C
> The required airflow is then 78 m3/hour: the fan sized for this airflow is the KVA 100 model.
(Note: When selecting your fans, always allow a 10% margin to compensate for airflow loss due to filter clogging)
> Do you still have a doubt or a further question about our fans? Contact us!