KVA (fans)

Side-mounted fans range

Key features:

  • Quick assembly (using clips)
  • Extra flat dimensions
  • Included: fan + filter grid
  • Wide range of electrical voltages
Request a quote

In standard

  • Included: fan (blower) + grid with replaceable filter (KFA)
  • Quick side mounting with clips
  • Ball bearing fans (MTBF 30,000 h at 55 °C)
  • Self-extinguishing according to UL 94-VO
  • RAL 7035 or 7032 paint
  • Complete documentation
  • 18-month warranty (unless otherwise agreed)

Options and adaptations

  • Numerous voltage options (24 VDC, 48 VDC, 115 VAC, 230 VAC, 400 VAC…)
  • EMC (electromagnetic compatibility) versions
  • Additional interchangeable filters (KFA type 25 / 50 / 100 / 200 / 500)

▶ TO BE SPECIFIED IN YOUR REQUEST

KVA fans intake grids

Fans intake grids

KVA side blower fans

KVA side blower fans

KVA fans filters

KVA fans filters

Technical specifications


KVA
025-230
KVA
050-230
KVA
050-110
KVA
100-110
KVA
100-230
KVA
120-230
KVA
120-110
Power supply Type AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Single-phase
V-Hz 230-1-50/60 230-1-50/60 115-1-50/60 115-1-50/60 230-1-50/60 230-1-50/60 115-1-50/60
Power consumption W 13 (12*) 22 (21*) 22 (21*) 22 (21*) 22 (21*) 24 (23*) 24 (23*)
Input current
nominal
A 0.10 (0.08*) 0.14 (0.12*) 0.26 (0.24*) 0.26 (0.24*) 0.14 (0.12*) 0.15 (0.13*) 0.30 (0.26*)
Electrical connection mm² FASTON 2.8 x 0.5 FASTON 2.8 x 0.5 FASTON 2.8 x 0.5 FASTON 2.8 x 0.5 FASTON 2.8 x 0.5 FASTON 2.8 x 0.5 FASTON 2.8 x 0.5
Waterproof index IP 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1
Nominal air flow m3/h 24 (28*) 55 (60*) 55 (60*) 100 (110*) 100 (110*) 120 (130*) 120 (130*)
Air flow with filter m3/h 14 (17*) 40 (45*) 40 (45*) 75 (90*) 75 (90*) 92 (105*) 92 (105*)
Type of filter   KFA 25 KFA 50 KFA 50 KFA 100 KFA 100 KFA 200 KFA 200
Air flow direction**   NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL
Operating temperature
ambient mini / maxi
°C -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70
Noise level dB(A) 30 (35*) 43 (49*) 43 (49*) 43 (49*) 43 (49*) 43 (49*) 43 (49*)
Weights kg 0.38 0.78 0.78 1.00 1.00 1.25 1.25
* Values at 60 Hz
** Airflow direction: N (normal) = from outside to inside / INV (reversed) = from inside to outside
Non-contractual values

 

KVA
200-230
KVA
200-110
KVA
500-230
KVA
500-110
KVA
500-110 inv
KVA
500-400
Power supply Type AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Single-phase
AC – Alternating
Three-phase
V-Hz 230-1-50/60 230-1-50/60 230-1-50/60 115-1-50/60 115-1-50/60 230-1-50/60
Power consumption W 40 (38*) 40 (38*) 70 (90*) 70 (90*) 70 (90*) 60 (70*)
Rated current
nominal
A 0.17 (0.16*) 0.34 (0.32*) 0.40 (0.38*) 0.80 (0.76*) 0.80 (0.76*) 0.18 (0.15*)
Electrical connection mm² FASTON 3 x 2.5 FASTON 3 x 2.5 FASTON 3 x 2.5 FASTON 3 x 2.5 FASTON 3 x 2.5 FASTON 3 x 2.5
Waterproof index IP 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1
Nominal air flow m3/h 230 (260*) 230 (260*) 500 (570*) 500 (570*) 500 (570*) 500 (570*)
Air flow with filter m3/h 95 (105*) 180 (210*) 370 (410*) 370 (410*) 370 (410*) 370 (410*)
Type of filter   KFA 200 KFA 200 KFA 500 KFA 500 KFA 500 KFA 500
Air flow direction**   NORMAL NORMAL NORMAL NORMAL REVERSE NORMAL
Operating temperature
ambient mini / maxi
°C -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70
Noise level dB(A) 53 (58*) 53 (58*) 65 (68*) 65 (68*) 65 (68*) 65 (68*)
Weights kg 1.60 1.60 3.00 3.00 3.00 3.00
* Values at 60 Hz
** Airflow direction: N (normal) = from outside to inside / INV (reversed) = from inside to outside
Non-contractual values / More information about air conditioning and cooling systems can be found on AFCE.

 

KVA
050-024
KVA
050-048
KVA
100-024
KVA
100-048
KVA
120-024
KVA
120-048
KVA
200-024
KVA
200-048
Power supply Type DC – Direct DC – Direct DC – Direct DC – Direct DC – Direct DC – Direct DC – Direct DC – Direct
V-Hz 24 VDC 48 VDC 24 VDC 48 VDC 24 VDC 48 VDC 24 VDC 48 VDC
Power consumption W 9 13 9 13 9 13 26 33
Rated current
nominal
A 0.37 0.27 0.37 0.27 0.37 0.27 1.08 0.68
Electrical connection mm²  2×1.5  2×1.5  2×1.5  2×1.5  2×1.5  2×1.5  2×1.5  2×1.5
Waterproof index IP 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1 54 class 1
Nominal air flow m3/h 55 55 100 100 120 120 180 180
Air flow with filter m3/h 40 40 75 75 95 95 180 180
Type of filter   KFA 50 KFA 50 KFA 100 KFA 100 KFA 200 KFA 200 KFA 200 KFA 200
Air flow direction**   NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL
Operating temperature
ambient mini / maxi
°C -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70 -10 / +70
Noise level dB(A) 45 45 45 45 45 45 61 61
Weights kg 0.47 0.47 0.70 0.70 0.95 0.95 1.2 1.2
** Airflow direction: N (normal) = from outside to inside / INV (reversed) = from inside to outside
Non-contractual values / More information about air conditioning and cooling systems can be found on AFCE.

 

 

Going further: selection of KVA fans


To help you select your product, EURODIFROID provides this fans selection diagram.

An example?

  • You need a power dissipation (cooling) capacity of 500 W
  • Your indoor/outdoor temperature difference is 20°C

> The required airflow is then 78 m3/hour: the fan sized for this airflow is the KVA 100 model.

(Note: When selecting your fans, always allow a 10% margin to compensate for airflow loss due to filter clogging)

> Do you still have a doubt or a further question about our fans? Contact us!

Discover similar solutions


Eurodifroid KVA side-mount fans
side-mounted fans
KVA (fans)
Read more
TEA range of top-mounted fans
Top-mounted fans
TEA (fans)
Read more
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.