KVA / KFA - Fans and filters

Ventilateurs et filtres

Fans and filters extra slim specially design to cool electrical enclosures

  • Air flow from 24 to 500 m3/h
  • Fast installation with clips
  • IP54
  • Ball-bearing fans (MTBF: 30 000 h at 55°C)
  • Auto-extinguishing ( UL 94-VO)
  • RAL 7035 or RAL 7032 painted
  • Several types of power supplies available (24 VDC, 48 VDC, 115 VAC, 230 VAC, tri 400 VAC on KVA 500)
  • Available in CEM version ( elecromagnetic compatibility)

Filter compatible with each fan size

Selection diagram

KFA-KVA fans and filters for electrical enclosures

Example:
Power to be dissipated: 500 W
Temperature delta: 20°C
Required air flow rate: 78 m3/h
Optimal fan: KVA 100 + KFA 100

NB: To select the optimal fan, please add a 10% margin to the theorical required air flow rate to take into account an additionnal pressure drop due to filter clogging.

KVA AC alternative current

KVA 025-230

KVA 050-230

KVA 050-110

KVA 100-110

KVA 100-230

KVA 120-230

KVA 120-110

Power supply

V-Hz

230-1-50/60

230-1-50/60

115-1-50/60

115-1-50/60

230-1-50/60

230-1-50/60

115-1-50/60

Air flow

m³/h

24(28*)

55(60*)

55(60*)

100(110*)

100(110*)

120(130*)

120(130*)

Air flow with KVA

m³/h

14(17*)

40(45*)

40(45*)

75(90*)

75(90*)

92(105*)

95(105*)

Power consumption

W

13(12*)

22(21*)

22(21*)

22(21*)

22(21*)

24(23*)

24(23*)

Running current

A

0,10(0,08*)

0,14(0,12*)(

0,26(0,24*)

0,26(0,24*)

0,14(0,12*)

0,15(0,13*)

0,30(0,26*)

Electric connection

FASTON 2,8x0,5mm²

Temperature

°C

-10/+70

IP

54 Classe 1

Sound level

dB(A)

30(35*)

43(49*)

43(49*)

43(49*)

43(49*)

43(49*)

43(49*)

Associated filter

KFA 25

KFA 050

KFA 050

KFA 100

KFA 100

KFA 200

KFA 200

Weight

kg

0,380

0,780

0,780

1,00

1,00

1,25

1,25

Air flow direction**

N/INV

N


KVA 200-230

KVA 200-110

KVA 500-230

KVA 500-110

KVA 500-110 inv

KVA 500-400

Power supply

V-Hz

230-1-50/60

230-1-50/60

230-1-50/60

115-1-50/60

115-1-50/60

400-3-50/60

Air flow

m³/h

230(260*)

230(260*)

500(570*)

500(570*)

500(570*)

500(570*)

Air flow with KFA

m³/h

95(105*)

180(210*)

180(210*)

370(410*)

370(410*)

370(410*)

Power consumption

W

40(38*)

40(38*)

70(90*)

70(90*)

70(90*)

60(70*)

Running current

A

0,17(0,16*)

0,34(0,32*)(

0,40(0,38*)

0,80(0,76*)

0,80(0,76*)

0,18(0,15*)

Electric connection

FASTON 3x2,5mm²

Temperature

°C

-10/+70

IP

54 Classe 1

Sound level

dB(A)

53(58*)

53(58*)

65(68*)

65(68*)

65(68*)

65(68*)

Associated filter

KFA 200

KFA 200

KFA 500

KFA 500

KFA 500

KFA 500

Weight

kg

1,6

1,6

3

3

3

3

Air flow direction**

N/INV

N

INV

N

*Datas given to 60Hz
**Air flow direction:N(nomal)=> from outside to inside / INV(reverse)=> from inside to outside

KVA DC direct current

KVA 050-024

KVA 050-048

KVA 100-024

KVA 100-048

KVA 120-024

KVA 120-048

KVA 200-024

KVA 200-048

Power supply

V-Hz

24 VDC

48 VDC

24 VDC

48 VDC

24 VDC

24 VDC

24 VDC

48 VDC

Air flow

m³/h

55

55

100

100

120

120

230

230

Air flow with KFA

m³/h

40

40

75

75

95

95

180

180

Power consumption

W

9

13

9

13

9

13

26

33

Running current

A

0,37

0,27

0,37

0,27

0,37

0,27

1,08

0,68

Electric connection

Bornier 2x1,5mm²

Bornier 2x2,5mm²

Temperature

°C

-10/+70

IP

54 Classe 1

Sound level

dB(A)

45

61

Associated filter

KFA 050

KFA 050

KFA 100

KFA 100

KFA 200

KFA 200

KFA 200

KFA 200

Weight

kg

0,470

0,470

0,700

0,700

0,950

0,950

1,20

1,20