Laser machine cooling solution

EURODIFROID conducted a chillers retrofitting project with range ECB water cooling devices, which were fitted into a specific frame "electrical cabinet" like, in order to optimize the space required on the floor.

EURODIFROID solution

*Datas given at 10°C water outlet, 32°C ambient temperature
Product ECB 400 TWI and ECB 900 TWI
Quantity 10 units
Cooling capacity* 25 kW et 70 kW
Technology Water cooler condenser water

Installed equipment

Design illustrations below (3D views) allow to have a preview of the EURODIFROID machine and the potential benefits of an integrated approach in the cabinet:


  • Small footprint
  • Accessibility of components
  • Full dismantling of the side panels and rear
  • Robust and bearing structure


EURODIFROID relies on its capacity to adapt a "standard" machine to complex industrial application (in this case, dirty water)

EURODIFROID advantages: Option monitoring fouling:

The fouling of the condenser is followed by a measurement of pressure losses in the condenser. The "monitoring fouling" option consists of the following components:

 

  • 1 differential pressure switch with upstream and downstream pressure tap
  • Actuating a dry contact to lift a fault "clogging"
  • The fault is adjustable (by pressure difference Maximum permissible nominal operation of the cooler)


This fault will light a red light to alert maintenance teams that maximum is exceeded and fouling a cleaning operation is required.

Global view of careened equipment
Water cooler water condenser
Chiller internal design
Water cooler water condenser
Global view of careened equpiment
Water cooler water condenser
Chiller internal design
Water cooler water condenser

Technical datas

*Datas given at 10°C water outlet, 32°C ambient temperature
Product:ECB400
Power supply:400V-3-50Hz
Cooling capacity*:25 000W
Power consumption:19 500W
Running current:34 A
Starting current:180 A
Line protection:40 A
Refrigerant:R134a
Refrigerant capacity:6,5 kg
Outlet temperature:10°C
Ambient temperature mini/maxi:15/45°C
Control temperature mini/maxi:10/25°C
Pump flow mini/maxi:120/300 l/min
Pump pressure mini/maxi:2,3/2,8 bar
Noise:75 dB(A)
Tank capacity:92 l
Weight:515 kg
*Datas given at 10°C water outlet, 32°C ambient temperature
Product:ECB900
Power supply:400V-3-50Hz
Cooling capacity*:70 000W
Power consumption:29 200W
running current:74 A
Starting current:413 A
Line protection:90 A
Refrigerant:R134a
Refrigerant capacity:8,3+7,5 kg
Outlet temperature:10°C
Ambient temperature mini/maxi:15/45°C
Control temperature mini/maxi:10/25°C
Pump flow mini/maxi:150/420 l/min
Pump pressure mini/maxi:2,1/4,4 bar
Noise:75 dB(A)
Tank capacity:150 l