EURODIFROID conducted a chillers retrofitting project with range ECB water cooling devices, which were fitted into a specific frame "electrical cabinet" like, in order to optimize the space required on the floor.
Product | ECB 400 TWI and ECB 900 TWI |
Quantity | 10 units |
Cooling capacity* | 25 kW et 70 kW |
Technology | Water cooler condenser water |
Design illustrations below (3D views) allow to have a preview of the EURODIFROID machine and the potential benefits of an integrated approach in the cabinet:
EURODIFROID relies on its capacity to adapt a "standard" machine to complex industrial application (in this case, dirty water)
EURODIFROID advantages: Option monitoring fouling:
The fouling of the condenser is followed by a measurement of pressure losses in the condenser. The "monitoring fouling" option consists of the following components:
This fault will light a red light to alert maintenance teams that maximum is exceeded and fouling a cleaning operation is required.
Product: | ECB400 |
Power supply: | 400V-3-50Hz |
Cooling capacity*: | 25 000W |
Power consumption: | 19 500W |
Running current: | 34 A |
Starting current: | 180 A |
Line protection: | 40 A |
Refrigerant: | R134a |
Refrigerant capacity: | 6,5 kg |
Outlet temperature: | 10°C |
Ambient temperature mini/maxi: | 15/45°C |
Control temperature mini/maxi: | 10/25°C |
Pump flow mini/maxi: | 120/300 l/min |
Pump pressure mini/maxi: | 2,3/2,8 bar |
Noise: | 75 dB(A) |
Tank capacity: | 92 l |
Weight: | 515 kg |
Product: | ECB900 |
Power supply: | 400V-3-50Hz |
Cooling capacity*: | 70 000W |
Power consumption: | 29 200W |
running current: | 74 A |
Starting current: | 413 A |
Line protection: | 90 A |
Refrigerant: | R134a |
Refrigerant capacity: | 8,3+7,5 kg |
Outlet temperature: | 10°C |
Ambient temperature mini/maxi: | 15/45°C |
Control temperature mini/maxi: | 10/25°C |
Pump flow mini/maxi: | 150/420 l/min |
Pump pressure mini/maxi: | 2,1/4,4 bar |
Noise: | 75 dB(A) |
Tank capacity: | 150 l |
Weight: | 1015 kg |